- IBC 2024 references ASCE 7-22
- Risk Category Based Design: Each Risk Category has its own map with corresponding wind speed
- No Importance Factor used when calculating Design Wind Pressure
- Major Updates: New tornado load provisions, updated wind speed maps, enhanced seismic design requirements
Roof Live Load (Lr)
- Standard: 20 PSF (Some local jurisdictions may require heavier loads)
- Live Load Reduction: Can be reduced to as low as 12 PSF for primary framing based on roof plane size and bay spacing
- Definition: Loads produced during maintenance by workers, equipment, materials, and movable objects (excludes Wind, Snow, Seismic, Dead Loads)
Floor Live Loads
- First Floor: XX PSF (Ground Floor design)
- Second Floor: XX PSF (Usually 2nd Floor or Mezzanine)
- Minimum: Must meet Table 1607.1 IBC requirements based on occupancy
Wind Speed & Exposure
- Basic Wind Speed: 3-second gust from IBC 2024 Fig. 1609.3 or ASCE 7-22 Fig.26.5-1
- Ultimate Wind Speed (VULT): IBC 2024/ASCE 7-22 values with updated velocity pressure equations
- Updated Maps: Enhanced wind speed maps based on recent climate data and extreme weather events
Wind Exposure Categories
| Category |
Description |
Surface Roughness |
| B |
Urban and suburban areas |
Enclosed |
| C |
Open terrain with scattered obstructions |
Most Common |
| D |
Flat, unobstructed areas adjacent to open water |
Lakes, Rivers, Ocean |
Wind Enclosure Classifications *
*Can be system calculated based on wall opening type input
| Classification |
Description |
GCpi Value |
| Open |
All walls open ≥80% total area |
0 |
| Partially Enclosed |
Windward wall open areas ≥110% of other walls AND windward open area < smaller of 4 ft² or 1% AND remainder <20% |
±0.55 |
| Enclosed |
All wall open areas < smaller of 4 ft² or 1% |
±0.18 |
| Partially Open |
Not Open, Partially Enclosed, or Enclosed |
±0.18 |
Tornado Loads (NEW in IBC 2024)
- Tornado Wind Speed: Based on Enhanced Fujita Scale
- Application: Required for Risk Category III & IV structures in tornado-prone regions
- Design Criteria: Enhanced anchoring and connection requirements
Load Applications
- Main Wind Force Resistance: Wind loads on frames and bracing
- Component & Cladding: Wind loads on purlins, girts, panels, endwall columns
Ground Snow Load (Pg)
- Definition: Maximum expected snow at ground elevation for 50-year Mean Recurrence Interval
- Value: XX PSF (Location specific)
- Updated Maps: Refined snow load data incorporating climate change projections and recent extreme weather patterns
Roof Snow Load Calculation
Formula:Pf = 0.7 × Ce × Ct × Is × Pg
Snow Exposure Factor (Ce)
| Exposure |
Category B |
Category C |
Category D |
| Fully Exposed |
0.9 |
0.9 |
0.8 |
| Partially Exposed |
1.0 |
1.0 |
0.9 |
| Sheltered |
1.2 |
1.1 |
1.0 |
Thermal Factor (Ct)
| Condition |
Coefficient |
| Heated |
1.0 |
| Above Freezing |
1.0 |
| Unheated |
1.1 |
| Intentionally Kept Below Freezing |
1.2 |
Snow Importance Factor (Is)
| Risk Category |
Occupancy |
Coefficient |
| I |
Agricultural, Minor Storage |
0.8 |
| II |
All Other |
1.0 |
| III |
Assembly >300 people |
1.1 |
| IV |
Essential Facilities |
1.2 |
Spectral Response Accelerations (USGS Maps)
- Ss: Short Period Acceleration (0.2 sec) - Always larger than S1
- S1: Long Period Acceleration (1.0 sec)
- Updated Parameters: Enhanced seismic hazard maps incorporating recent seismological research and ground motion prediction models
Design Accelerations (Calculated by eQuote360)
SDS = (2/3) × Sms where Sms = Fa × Ss SD1 = (2/3) × Sm1 where Sm1 = Fv × S1
- Fa & Fv: Based on site class and spectral accelerations
Site Classes
| Class |
Description |
| A* |
Hard Rock |
| B* |
Rock |
| C* |
Very Dense Soil & Soft Rock |
| D |
Stiff Soil (Default) |
| E |
Soft Soil |
| F* |
Special Study Required |
*Requires soils report or sealed document
Seismic Design Categories
- Categories D+: Require special inspections, pre-tensioned bolts, and special detailing requirements
- Analysis Method: Equivalent Lateral Force (used by eQuote360)
- Response Modification Factor (R) 3.0 for Categories A-C (Updated values for other categories)
- Reference: ASCE 7-22 Table 12.2-1(H) - Steel Systems not detailed for seismic resistance
Seismic Importance Factor (Ie)
| Risk Category |
Coefficient |
| I |
1.0 |
| II |
1.0 |
| III |
1.25 |
| IV |
1.50 |
Dead Load
- Definition: Self-weight of building system construction
- Value: Calculated based on materials
- Updated Requirements: Enhanced consideration for modern building materials and systems
Collateral Load
- Definition: Weight of additional permanent materials (sprinklers, HVAC, electrical, partitions, ceilings)
- Typical Value: XX PSF
Typical Collateral Load Components
| Component |
Weight (PSF) |
| Gypsum Board |
1/2" = 2 PSF, 5/8" = 3 PSF |
| Acoustical Tile |
1 PSF |
| Lighting |
0.5-2 PSF |
| HVAC |
1-3 PSF |
| Sprinkler |
Dry = 1.5-3 PSF, Wet = 3-5 PSF |
| Solar Panels |
2-4 PSF (NEW consideration) |
| Battery Storage |
10-20 PSF (NEW consideration) |
Design Rain Load
- Updated Formula: Enhanced calculations incorporating climate change impacts
Ponding Load Considerations
- Improved requirements for extreme precipitation events
- Enhanced calculation methods for secondary drainage systems
- Updated deflection limits to prevent progressive ponding
- Climate resilience factors
Definition
Movement of structure relative to supports due to applied loads
Standard Limits
| Member Type |
Deflection Limit |
| Rafters/Purlins |
L/180 |
| With Ceiling |
L/240 |
| Special Cases |
L/360 |
| Column Height |
H/240 (typical), H/90 (special) |
Calculation Examples
- 25'-0" beam: 25' × 12 = 300"
- L/180: 300"/180 = 1.67" maximum deflection
- 20'-0" column: 20' × 12 = 240"
- H/240: 240"/240 = 1.0" maximum deflection
- H/90: 240"/90 = 2.67" maximum deflection
Per IBC 2024 Section 1605.2:
Basic Combinations
- 1.4D
- 1.2D+1.6L+0.5 (L_r \text{ or } S \text{ or } R)
- 1.2D + 1.6(L_r \text{ or } S \text{ or } R) + (1.0L \text{ or } 0.5W)
- 1.2D + 1.0W + 1.0L + 0.5(L_r \text{ or } S \text{ or } R)
- 1.2D+1.0E+1.0L+0.2S
- 0.9D+1.0W
- 0.9D+1.0E
Special Combinations (Updated)
- Flood: 1.2D + 1.0F_a + 1.0L
- Atmospheric Ice: 1.2D + 1.0D_i + 1.0L + 0.2S
- Tornado (NEW): 1.2D + 1.0T + 1.0L
- Enhanced Rain: Updated rain load combinations per ASCE 7-22
Climate Change Considerations
- Enhanced extreme weather provisions
- Updated temperature ranges for thermal effects
- Increased precipitation factors
- Wind speed adjustments for changing climate patterns
Sustainability Requirements
- Energy efficiency provisions
- Renewable energy integration considerations
- Resilient design requirements for essential facilities
Useful Resources
Units & Conversions
- PSF: Pounds per Square Foot
- PLF: Pounds per Linear Foot
- KSI: Kips per Square Inch
- PSI: Pounds per Square Inch (1 PSI = 144 PSF)
- Kip: 1,000 pounds
- MPH: Miles per Hour
Key Organizations
- ASCE: American Society of Civil Engineers
- AISC: American Institute of Steel Construction
- AISI: American Iron and Steel Institute
- IBC: International Building Code
- MBMA: Metal Building Manufacturers Association
- USGS: US Geological Survey
- UFC: Unified Forces Command
Category Definitions
| Category |
Description |
Examples |
| I |
Low Hazard |
Agricultural, Minor Storage |
| II |
Normal |
Standard Commercial/Industrial |
| III |
High Occupancy |
Assembly >300 people |
| IV |
Essential |
Hospitals, Fire Stations, Emergency Shelters, Public Utilities |
Important Notes
- MRI: Mean Recurrence Interval (2% chance = 50-year MRI)
- Occupancy: Chapter 16 definition (NOT Chapter 3 occupancy)
- Longitude: Must be negative for US locations when using USGS tools
- GPS Coordinates: Available in Google Maps by placing cursor over location
- Tornado Load Provisions: New requirements for tornado-resistant design
- Climate Resilience: Enhanced provisions for extreme weather events
- Updated Wind Maps: Refined wind speed data incorporating recent climate research
- Enhanced Seismic Provisions: Updated ground motion parameters and site coefficients
- Sustainability Integration: Requirements for renewable energy and resilient design
- Solar Panel Considerations: Updated dead load provisions for rooftop solar installations
- Battery Storage Systems: New provisions for energy storage system loads
- Hydrostatic Loads: Standing water pressure
- Hydrodynamic Loads: Moving water forces
- Wave Loads: Breaking wave impacts
- Debris Impact Loads: Floating debris collision forces
- Sea Level Rise: Updated base flood elevations incorporating climate projections
- Enhanced Access Requirements: Improved provisions for equipment maintenance access
- Safety Systems: Updated requirements for fall protection and emergency egress
- Inspection Access: Clear requirements for structural inspection accessibility
This cheat sheet is designed for use with eQuote360 metal building design software and should be used in conjunction with the complete IBC 2024 and ASCE 7-22 standards . This represents the most current building code requirements as of 2024 .
GET THE LATEST CODE-COMPLIANT DESIGNS
At eQuote360.com, we specialize in connecting your project with professionals who are experts in the IBC 2024 and ASCE 7-22 standards.
START YOUR NEXT PROJECT:
- Get quotes from IBC 2024-certified metal building specialists
- Access software tools for accurate load calculations
- Connect with regional code compliance experts